Signal On Alarm - Endress+Hauser Proline Promag P 200 Technical Information

Electromagnetic flow measuring system
Table of Contents

Advertisement

Proline Promag P 200

Signal on alarm

Endress+Hauser
Pulse/frequency/switch output
Function
Version
Maximum input values
Voltage drop
Residual current
Pulse output
Pulse width
Maximum pulse rate
Pulse value
Assignable measured
variables
Frequency output
Output frequency
Damping
Pulse/pause ratio
Assignable measured
variables
Switch output
Switching behavior
Switching delay
Number of switching cycles Unlimited
Assignable functions
Depending on the interface, failure information is displayed as follows:
Current output
4-20 mA
Failure mode
HART
Device diagnostics
Device condition can be read out via HART Command 48
Can be set to pulse, frequency or switch output
Passive, open collector
• DC 35 V
• 50 mA
For information on the Ex connection values (® ä 9)
• For £ 2 mA: 2 V
• For 10 mA: 8 V
£ 0.05 mA
Adjustable:5 to 2 000 ms
100 Impulse/s
Adjustable
• Volume flow
• Mass flow
Adjustable:0 to 1 000 Hz
Adjustable:0 to 999 s
1:1
• Volume flow
• Mass flow
Binary, conductive or non-conductive
Adjustable:0 to 100 s
• Off
• On
• Diagnostic behavior
• Limit value
– Volume flow
– Mass flow
• Flow direction monitoring
• Status
– Empty pipe detection
– Low flow cut off
Selectable (as per NAMUR recommendation NE 43):
• Minimum value: 3.6 mA
• Maximum value: 22 mA
• Defined value:3.59 to 22.5 mA
• Actual value
• Last valid value
7