6 Troubleshooting
 Default
Register name
Description
Range
Details
Detection timing
Recovery
Effects
Cause and cor-
rection
Precautions/
Remarks
 FileConfigErr
Register name
Description
Range
Details
Detection timing
Recovery
Effects
Cause and cor-
rection
Precautions/
Remarks
6-14
Sys.Default
Initialized to the factory default setting.
0 to 1
0: No error
1: Cases below
In the factory default state, or initialized to the factory default state by a re-initializa-
tion command ($$$***).
Configuration changed after save command was issued.
When power is turned ON or reset
Cycle the power supply, reset command ($$$)
Operation continues
Cause (Assumed cause)
Re-initialization command
($$$***) issued.
HWChangeErr or
ConfigLoadErr occurred.
None
Sys.FileConfigErr
System file setting error
0 to 1
0: No error
1: System file setting error
When power is turned ON or reset
Cycle the power supply, reset command ($$$)
Operate at default settings.
Cause (Assumed cause)
System file settings are in-
correct.
The CPU Unit or the CK3W
Unit has failed
None
CK3M-series Programmable Multi-Axis Controller User's Manual Hardware (O036)
Correction
None
Check the corrective action
for each error.
Correction
If the re-initialization com-
mand ($$$***) is executed,
and the error no longer oc-
curs, review the user pro-
gram.
If this error persists even
after you make the above
corrections, replace the
CPU Unit or the CK3W
Unit.
Prevention
None
None
Prevention
None
None