Siemens SIMATIC ET 200SP HA Manual page 8

Analog input module ai 16xi 2-wire hart ha ( 6dl1134-6th00-0ph1)
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

Product overview
2.1 Properties of the AI 16xI 2-wire HART HA I/O module
● The analog inputs have the following channel-specific parameterizable properties:
– Current measurement type for 2-wire HART transmitter
– Measuring range 0 to 20 mA, 0 to 10 mA, 4 to 20 mA and 4 to 20 mA with HART
– Resolution dependent on measuring range and interference frequency suppression,
– Smoothing
– Interference frequency suppression 10 Hz, 50 Hz and 60 Hz
● Channel-specific configurable diagnostics
● Module-specific configurable diagnostics for missing supply voltage L+
● Hardware interrupt at limit violation, per channel (two high and two low limits each)
The module supports the following functions:
● Firmware update
● I&M identification data
● Parameter reassignment in RUN
● Value status QI
● IO redundancy
● HART communication (Rev. 5 to Rev. 7)
● Up to 8 HART variables directly in the input address area
● A multiHART area in the input/output area
You can configure the I/O module with HW Config and integrate it into your system.
Accessories
The following accessories must be ordered separately:
● Labeling strips
● Color-coded labels
● Reference identification label
● Shield connector
8
minimum 15 bits including sign, maximum 16 bits including sign
Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1)
Manual, 11/2017, A5E39408968-AB