HART operating data records
B.6 HART-specific settings
B.6

HART-specific settings

HART communication is available via standard parameter assignment.
You can specify additional HART-specific settings on a channel-specific basis using data
records 131...146.
The parameters assigned with STEP 7 are not changed permanently in the CPU, which means
the parameters assigned with STEP 7 are valid again after a restart.
Every new parameter assignment of the analog module resets the HART-specific settings back
to the initial values from parameter data record 128.
The I/O module does not apply the HART-specific settings if there is missing supply voltage L
+.
If you make changes in IO redundancy mode using the HART-specific settings, these changes
only apply to the addressed module or the addressed channel. There is no synchronization
with the partner channel.
Channel
0
1
2
3
:
:
15
72
Data record number
131
132
133
134
146
Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1)
Manual, 11/2017, A5E39408968-AB