Siemens SIMATIC ET 200SP HA Manual page 62

Analog input module ai 16xi 2-wire hart ha ( 6dl1134-6th00-0ph1)
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

HART operating data records
B.1 HART command interface
set SHC bit is detected for this channel, or if no further command is received for the channel
within 2 seconds of the previous HART command.
Reading/writing data in RUN
HART operating data records are transferred to the module with the instruction "WRREC" and
read by the module with the instruction "RDREC".
Errors during the transfer are indicated at output parameter STATUS of the "WRREC" or
"RDREC".
The following HART operating data records are available:
Data record
number
80
81
82
83
:
:
110
111
121
131
132
:
:
146
148
149
62
Description
HART job channel 0
HART response channel 0
HART job channel 1
HART response channel 1
HART job channel 15
HART response channel 15
HART variables
HART parameter channel 0
HART parameter channel 1
HART parameter channel 15
HART directory
HART feature data
Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1)
Length
Writable
(bytes)
240
Yes
240
No
240
Yes
240
No
240
Yes
240
No
320
No
8
Yes
8
Yes
8
Yes
17
No
3
No
Manual, 11/2017, A5E39408968-AB
Readable
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents