Parameters

4.2 Module/channel parameters

4.2
Module/channel parameters
Parameters of AI 16xI 2-wire HART HA
You have the following setting options:
Table 4-1
Parameters and their default settings
Parameter
Diagnostics, Missing supply
voltage L+
IO redundancy
Potential group
Measurement type
Measuring range
Diagnostics encoder supply ● Enabled
Diagnostic short-circuit to L+ ● Enabled
Diagnostics overflow
Diagnostics underflow
Diagnostics, Wire break
Diagnostics HART
14
Value range
● Enabled
● Disabled
● None
● 2 modules
● Use potential group of the left
module
● Allow new potential group
● Disabled
● Current (2-wire transducer)
● 0 to 10 mA
● 0 to 20 mA
● 4 to 20 mA
● 4 to 20 mA HART
There is no underrange in the
ranges 0 to 10 mA or 0 to 20 mA
That is, the smallest analog value
is zero.
● Disabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
Default
Enabled
None
Use potential group
of the left module
Current (2-wire
transducer)
4 to 20 mA HART
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1)
Parame‐
Efficiency range
ter reas‐
signment
in RUN
Yes
Module
Yes
Module
No
Module
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Manual, 11/2017, A5E39408968-AB