Maintenance
Error
message
code
Retentive memo‐
154
H
ry in carrier mod‐
ule defective
Retentive memo‐
155
H
ry in the terminal
block defective
Response of the HART configuration changed maintenance message
1
If the HART field device signals "parameter reassignment" (configuration changed) in the 2nd
status byte, the module generates the maintenance message "HART configuration changed".
If the field device withdraws the message in the 2nd status byte within a minute, the
maintenance message is also deleted again by the module. If the message in the 2nd status
byte is still set after a minute, the module then independently sends HART command 38 for
resetting the message in the field device.
Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1)
Manual, 11/2017, A5E39408968-AB
Drivers, parameters, diagnostics messages and address space
Assignment
Meaning / Cause
Module
Fault detected in the data block on the carri‐
er module during operation
Module
A memory block error was detected on the
terminal block during operation
A.5 Diagnostics messages and maintenance events
Remedy
Replace carrier module
Replace terminal block
55