Technical specifications
Note
With use of sensor supply U
Horizontal mounting position:
Up to 70°C, up to 12 channels when using the encoder supplies (total current of outputs
300 mA)
Up to 70°C, up to 16 channels when using the encoder supplies
Up to 65°C, up to 16 channels when using the encoder supplies (total current of outputs
400 mA)
Up to 60°C, up to 16 channels when using the encoder supplies (total current of outputs 2 A)
Vertical mounting position:
Up to 60°C, up to 12 channels when using the encoder supplies (total current of outputs
300 mA)
Up to 60°C, up to 16 channels without using the encoder supplies
Up to 55°C, up to 16 channels when using the encoder supplies (total current of outputs
400 mA)
Up to 50°C, up to 16 channels when using the encoder supplies (total current of outputs 2 A)
Maximum supply voltage ripple during HART operation
● 390 mVpp at 50 Hz
● 8.3 mVpp at 300 Hz
Cycle time
The cycle time describes the time slice in which signals from the inputs are acquired and
processed.
The cycle time depends on the parameter assignment and can be different for each channel.
Operating mode
Analog inputs for 60 Hz interference frequency
suppression
Analog inputs for 50 Hz interference frequency
suppression
Analog inputs for 10 Hz interference frequency
suppression
38
(terminal 17...32), the following derating must be observed:
Vn
Cycle time
16.6 ms
20 ms
100 ms
Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1)