Siemens SIMATIC ET 200SP HA Manual page 64

Analog input module ai 16xi 2-wire hart ha ( 6dl1134-6th00-0ph1)
Hide thumbs Also See for SIMATIC ET 200SP HA:
Table of Contents

Advertisement

HART operating data records
B.2 HART job and response data records
Structure of response data records 81, 83, 85, 87...111
In case of response error
Byte
0
1
2
3...239
In case of response error
Byte
0
1
2...239
Coding "Response control":
Bits 0-2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
Coding "HART group error display"
Bit number
0
1
2
64
Meaning
Response control
HART group error display
Protocol error
Response data according to HART specifica‐
tion
Meaning
Response control
HART group error display
Response data according to HART specifica‐
tion
Response result (processing status)
0 = Inactive
1 = Inactive (reserved)
2 = Waiting
3 = Waiting, executing
4 = Successful, with data
5 = Successful, without data
6 = Error, with data
7 = Error, without data
0 = Burst mode not active;
0 = Response data come directly from the HART device
0 = Response data in transparent message format
0 = SHC mode not active
1 = SHC mode active
0 = HART response
Meaning
Additional status information
available
HART communication error
Parameter check
Comment
Only present when "Response result" = 6
= "Error, with data"
Comment
Only present when "Response result" = 4
= "Successful, with data"
Explanation
(2nd HART status byte) You obtain additional status in‐
formation, if required, with HART command 48.
The field device has detected a communication error
when receiving the command. The error information is
in the first HART status byte
0: HMD parameters unchanged
1: Check HMD parameters
Analog Input Module AI 16xI 2-wire HART HA ( 6DL1134-6TH00-0PH1)