Safe Stop Of Vlt Automationdrive Fc302; General Warning - Danfoss VLT Center Winder MCO 352 Operating Instructions Manual

Table of Contents

Advertisement

2 Safety Instructions and General Warnings

2.2.5 Safe Stop of VLT AutomationDrive FC302

The VLT AutomationDrive FC 302 can perform the Designated Safety Function Uncontrolled Stopping by removal of power (as defined by draft IEC
2
61800-5-2) or Stop Category 0 (as defined in EN 60204-1). It is designed and approved suitable for the requirements of Safety Category 3 in EN 954-1.
This functionality is called Safe Stop. In order to install and use the Safe Stop function in accordance with the requirements of Safety Category 3 in EN
954-1, the related information and instructions of the VLT AutomationDrive FC 300 Design Guide MG.33.BX.YY must be followed! The information and
instructions of the Operating Instructions are not sufficient for a correct and safe use of the Safe Stop functionality!

2.2.6 General Warning

WARNING:
Touching the electrical parts may be fatal – even after the equipment has been disconnected from mains.
Also make sure that all voltage inputs have been disconnected, such as load-sharing (linkage of DC intermediate circuit), as well as the motor
connection for kinetic back-up.
Using VLT AutomationDrive FC 300 wait at least 15 minutes.
6
®
MG.33.T1.02 - VLT
is a registered Danfoss trademark
®
VLT
Center Winder MCO 352