5 Center Winder Calibration

5.1.4 Check Inputs

1. Check Input 3 "Winder Jog
Close Input 3. The winder should jog in the forward (over) direction.
Open Input 3.
The jog speed can be adjusted in parameter 19-07.
2. Check Input 2 "Winder Jog
Close Input 2. The winder should jog in the reverse (under) direction.
Open Input 2 "Jog Reverse".
The jog speed can be adjusted in parameter 19-07.
3. Check Input 1 "Over/Under
Close Input 1 "Over /Under Wind".
5
Close Input 3 winder should jog in the under direction.
Open Input 3 "Jog Forward".
Open Input 1 "Over /Under Wind".

5.1.5 Calibration of Diameter Measurement Signal

1.
Parameter 19-13 should be set to 1 to enable this feature.
2.
Mount the smallest core used on the winder.
3.
Set the LCP to display the signal at the analog input selected in parameter 19-14.
4.
Close Input 4 "Partial Roll Diameter".
5.
Close Input 8 "Diameter Reset".
6.
Record the voltage or current input value resulting from core diameter.
7.
Multiply the value by 100 and enter into parameter 19-15.
8.
Set the LCP to display Diameter.
9.
Mount a full roll or simulate a full-roll.
10.
Increase the value of parameter 19-15 until the displayed Diameter is as close to 100,000 as possible.
11.
The displayed Diameter should now sweep from the core diameter to the full-roll diameter (100,000) as the analog input moves through its full
range.
12.
Open Inputs 4 and 8 unless the Diameter will always be initially measured.