4 How to Install
19-05 Core1 Diameter
Range:
5000*
[5000 – 100000]
4
NB!
Note: Parameter 19-05 must be less than parameter 19-06.
19-06 Core2 Diameter
Range:
5000*
[5000 – 100000]
NB!
Parameter 19-05 must be less than parameter 19-06.
19-07 Winder Jog Speed
Range:
0%*
[0 – 100%]
NB!
Diameter is not taken into account to determine surface jog speed.
19-08 TLD Low Limit
Range:
0*
[-200 – 2000]
NB!
Setting the value to -200 will disable the low tension limit trip.
18
This parameter is intended to preset the diameter when a partial roll is loaded on the rewinder. If
Input 4 is ON when the diameter is reset with Input 8, the diameter will be preset to the value
programmed in this parameter. For unwinding applications, this parameter can be used to set the
full roll diameter.
Function:
100000 = 100 % of full roll, see parameter 19-04.
This parameter is programmed with the main core value to be used on the winder. This parameter
must be set for the smallest core diameter for both rewind and unwind applications.
Function:
100000 = 100 % of full roll, see Parameter 19-04.
This parameter allows programming a secondary core diameter if rewinding or a secondary full roll
diameter if unwinding.
Function:
Winder jog speed 100 = 100 % of the speed set in parameter 3-03 (MAX REFERENCE RPM).
This parameter sets the winder jog speed percentage. This speed is used for both forward and
reverse jogging. The jog ramp is fixed at 4 seconds.
Function:
1000 = 100.0 % tension.
This parameter is the low limit for the Tension Limit Detector.
®