Assembly

8
Assembly
Requirements for the installation site
14
WARNING!
Danger from hazardous substances!
Possible consequence: Fatal or very serious injuries.
Please ensure when handling hazardous substances
that you have read the latest safety data sheets provided
by the manufacture of the hazardous substance. The
actions required are described in the safety data sheet.
Check the safety data sheet regularly and replace, if
necessary, as the hazard potential of a substance can
be re-evaluated at any time based on new findings.
The system operator is responsible for ensuring that
these safety data sheets are available and that they are
kept up to date, as well as for producing an associated
hazard assessment for the workstations affected.
The operator must provide the following at the installation site:
1 - Water connection with eye bath
1 - Water connection for deionised water (diluting water and rinsing
water)
2 - Mains power sockets for both metering pumps
1 - Leak-tight pan provided by the customer around the installation loca‐
tion and suitable for hydrazine or a collecting pan - see "Accessories"
chapter.
The following parameters serve as a guideline for the operator, although
other or supplementary measures may be needed depending on the
installation site:
The installation location must be in a closed room with good ventila‐
n
tion.
The site of the hydrazine system must be protected against sun, frost-
n
proof and well ventilated.
The exhaust air must be able to rise upwards and outside or into a
n
bleed line.
It must be possible to fit the flushing adapter.
n
A horizontal, smooth and stable surface must be available for the
n
installation.
It must be possible to fasten the system to prevent if from toppling
n
over.
The operator must ensure that the system cannot be damaged
n
mechanically from internal traffic etc. If necessary, mount a guard
plate.
The operator must ensure that the system cannot be flooded at the
n
installation site.