ProMinent DULCODOS Hydrazin Operating Instructions Manual page 26

Hydrazine metering systems
Table of Contents

Advertisement

Maintenance
Interval
Maintenance work
every 6 months
Replace the active carbon filter - see section "Maintenance of active
carbon filter" below.
every two years
Replace the relief valve diaphragm - see operating instructions for the relief
valve.
Maintenance of the active carbon filter
26
WARNING!
Hydrazine can escape
Hydrazine may escape when carrying out the work listed
below.
Therefore always flush the system - see chapter
"Decommissioning and disposal"!
Refit the new active carbon filter to the metal bracket
so that it cannot break off!
Properly dispose of the active carbon filter!
1.
Flush the hydrazine metering system - see chapter "Decommis‐
sioning and disposal".
2.
Dismantle the used active carbon filter.
3.
Fit the new active carbon filter.
4.
Refit the new active carbon filter to the metal bracket so that it
cannot break off.
5.
Re-connect the exhaust air line to the active carbon filter
6.
Properly dispose of the used active carbon filter.
Personnel
Technical personnel
Technical personnel