Water Level Gauge Set (Sight Glass); Main Steam Valve - FULTON RB Series Installation, Operation And Maintenance Manual

Gas/oil/dual fuel horizontal steam boilers
Table of Contents

Advertisement

Fulton Ltd
2.6.2

WATER LEVEL GAUGE SET (SIGHT GLASS)

All RB/RBC series boilers are fitted with two, 'Clifton' type (unless otherwise specified) reflex
water level gauges.
The water level gauge blowdown valves should be connected to the auxiliary blowdown line; final
connection to the blowdown valves being via soft copper tubing.
The valve fittings are 6 mm.
2.7

MAIN STEAM VALVE

Distribution pipework should be run
from the main steam valve on top
of the boiler to the steam delivery
point(s). Care should be taken to
ensure that adequate condensate
drainage and expansion facilities are
provided within the pipework run(s).
To prevent excessive loads being
imposed on the main steam isolating
valve, the pipework should be secured
near the boiler, ensuring adequate
flexibility exists in the pipework
between the steam valve and the
securing point, to minimise any loads
imposed on the valve.
RB-RBC-IOMM-2015-1
Figure. 5 - Water Level Gauges
INSTALLATION - 2
Figure. 6 - Main Steam Valve
Main steam valve
Steam distribution
flange
Page 9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents