How to Install
6.5 Electrical Installation in General
NOTE
All cabling must comply with national and local
regulations on cable cross-sections and ambient
temperature. Copper conductors required, (60-75 °C)
recommended.
Power [kW]
Frame
1x200-240 V
3x200-240 V
M1
0.18-0.75
0.25-0.75
M2
1.5
1.5
M3
2.2
2.2-3.7
M4
M5
1)
Spade connectors (6.3 mm Faston plugs)
Table 6.2 Tightening of Terminals
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
®
VLT
Micro Drive FC 51 Design Guide
3x380-480 V
Line
Motor
0.37-0.75
1.4
0.7
1.5-2.2
1.4
0.7
3.0-7.5
1.4
0.7
11.0-15.0
1.3
1.3
18.5-22.0
1.3
1.3
®
MG02K202 - VLT
is a registered Danfoss trademark
Torque [Nm]
DC connection/Brake
Control Terminals
1)
Spade
0.15
Spade
1)
0.15
1)
0.15
Spade
1.3
0.15
1.3
0.15
Earth
Relay
3
0.5
3
0.5
3
0.5
3
0.5
6
6
3
0.5
49