How to Install
PLC etc.
PLC
Min. 16 mm
Equalizing cable
Control cables
Mains-supply
L1
L2
L3
PE
Reinforced protective earth
Illustration 6.9 EMC-correct Electrical Installation
NOTE
For North America use metal conduits instead of shielded
cables.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
®
VLT
Micro Drive FC 51 Design Guide
Panel
2
Min. 200mm
between control
cable, mains cable
and between mains
motor cable
®
MG02K202 - VLT
is a registered Danfoss trademark
Output con-
tactor etc.
Earthing rail
Cable insula-
tion stripped
All cable entries in
one side of panel
Motor cable
Motor, 3 phases and
Protective earth
6
6