REMEHA Quinta Ace 30 Installation And User Manual page 28

High-efficiency wall-hung gas boiler
Hide thumbs Also See for Quinta Ace 30:
Table of Contents

Advertisement

5 Installation
Fig.22
Blocking input
BL
Fig.23
Release input
RL
28
RL
Tout
Tdhw
AD-4100104-02
AD-3001303-01
Tab.19
Internal heating curve settings
Comfort base point
Steepness
(°C)
(parameter CP230)
(parameter CP210)
15
0.5
15
1.0
15
1.5
15
2.0
15
2.5
15
3.0
(1) See sample drawing
(2) Flow temperature is cut off at Ta (max) = parameter CP010 / CP000
Blocking input
The boiler has a blocking input (Normally Closed contact). This input
relates to the BL terminals of the connector.
If this contact is opened, the boiler will be blocked or locked out.
Change the function of the input with parameter setting AP001. This
parameter has the following 3 configuration options:
Complete blocking: no frost protection with the outside sensor and no
boiler frost protection (pump does not start and burner does not start)
Partial blocking: boiler frost protection (pump starts when the
temperature of the heat exchanger is < 6°C and the burner starts when
the temperature of the heat exchanger is < 3°C)
Lock out: no frost protection with outside sensor and partial boiler frost
protection (pump starts when the temperature of the heat exchanger is <
6°C, the burner does not start when the temperature of the heat
exchanger is < 3°C).
Important
First remove the bridge if this input is used.
Warning
Only suitable for potential-free contacts.
Release input
The boiler has a release input (Normally Open contact). This input relates
to the RL terminals of the connector.
If this contact is closed before there is a heat demand, the boiler will be
blocked after a waiting time. Change the waiting time of the input with
parameter setting AP008.
If this contact is closed during a heat demand, the boiler will be blocked
instantly.
Warning
Only suitable for potential-free contacts.
Connecting the calorifier sensor/thermostat
A calorifier sensor or thermostat can be connected to the Tdhw terminals
of the connector.
Ta (°C)
(where Tout = –10°C)
30
45
60
75
(1)
90
105
(2)
7684359 - v.06 - 10012019