REMEHA Quinta Ace 30 Installation And User Manual page 50

High-efficiency wall-hung gas boiler
Hide thumbs Also See for Quinta Ace 30:
Table of Contents

Advertisement

8 Settings
Code Display text
Description
GP0
Fan RPM
Minimum fan speed
08
Min
during Central
Heating + Domestic
Hot Water mode
GP0
Fan RPM
Fan speed at
09
Start
appliance start
GP0
GPS Check
Gas Pressure
10
Switch check on/off
GP0
Temp diff
Modulate back
21
Modulating
when delta
temperature is
large then this
treshold
GP0
Tfa Filter
Tau factor for
22
Tau
average flow
temperature
calculation
PP01
ChPumpDT
Reduction of
4
Reduction
temperature delta
modulating for
pump modulation
PP01
Max. CH
Maximum central
6
pump speed
heating pump
speed (%)
PP01
ChPumpSp
Maximum central
7
eedMaxFact
heating at minimum
or
load as percentage
of max pump
speed
PP01
Min CH
Minimum central
8
pump speed
heating pump
speed (%)
PP02
Start
Hysteresis to start
3
hysteresis
burner in heating
CH
mode
50
Range
Func­
tionGroup
1400 Rpm -
Gas fired
4000 Rpm
appliance
1000 Rpm -
Gas fired
4000 Rpm
appliance
0 = No
Gas fired
1 = Yes
appliance
10 °C - 40
Gas fired
°C
appliance
1 - 255
Gas fired
appliance
0 °C - 40 °C Gas fired
appliance
20 % - 100
Gas fired
%
appliance
0 % - 100 % Gas fired
appliance
20 % - 100
Gas fired
%
appliance
1 °C - 10 °C Gas fired
appliance
Navigation
30
45
Gas fired
1550 1550 1600 1600 1600 1750
appliance
Gas fired
2500 2500 2500 2500 2500 2500
appliance
Gas fired
0
0
appliance
Gas fired
25
25
appliance
Gas fired
1
1
appliance
Gas fired
18
18
appliance
Gas fired
100
100
appliance
Gas fired
100
100
appliance
Gas fired
30
30
appliance
Gas fired
10
10
appliance
55
65
90
115
0
0
0
0
25
25
25
20
1
1
1
1
18
18
18
18
100
100
100
100
100
100
100
100
30
30
30
30
10
10
10
10
7684359 - v.06 - 10012019