7.5.1 Setting method for auto refresh
Buffer memory and description of the item selected on the screen are displayed.
7 - 26
(1) Displaying the screen for auto refresh
For the method for displaying the screen, refer to Section 7.4.1.
(2) Setting auto refresh
Set a CPU module device that stores the information in the setting item field.
Applicable devices are any of X, Y, M, L, B, T, C, ST, D, W, R, and ZR.
(3) Writing setting values
Execute the writing of auto refresh settings to the CPU module, by Write to PLC.
For details of Write to PLC, refer to the GX Works2 Version1 Operating Manual
(Common).
(4) Enabling setting values
Enable the auto refresh settings by turning the power OFF
the CPU module.
7 SETTINGS FOR THE C24
ON or by resetting
7 - 26