Item
Element Name
Code Type
Setting Value
9 - 8
(2) Static Data
Use this element when a specific code/character string such as command exists
in a packet.
When sending: Sends a specified code and character string.
When receiving: Verifies the receive data.
Multiple Static Data elements can be placed to desired positions in the data
division.
The items are the same as ones explained in Section 9.3 (1) in this section.
(3) Terminator
This element indicates the end of a packet. Use this element when a
code/character string indicating the end of the packet is included.
The following table lists the items.
Set a name of the element.
Set a data type of the setting value.
ASCII String/ASCII Control Code/HEX
Set data within 1 to 50 bytes.
Code type
ASCII String
ASCII Control Code 00
HEX
POINT
Only one Terminator can be placed in a packet.
Only a Check code and Static Data can be placed behind a terminator.
9 DATA COMMUNICATION USING THE PREDEFINED PROTOCOL
Description
Setting range
20
to 7F
H
H
to 1F
, and 7F
of control code
H
H
H
00
to FF
of hexadecimal data
H
H
Remark
-
-
(Setting example)
ASCII String
: "ABC"
ASCII Control Code: STX
HEX
: FFFF