Section IX. Maintenance
9-1 Inspection and Maintenance
Under normal working conditions, in addition to daily inspection, the
frequency converter should be subject to regular inspection (for example
inspection for overhaul or as specified but at an interval of six months at
most). Please refer to the following table in order to prevent faults.
Check time
Check
Check item
point
D
R
LED and LCD
If there is any
Display
display
abnormal display
Cooling
If abnormal noise or
Fan
system
vibration is produced.
Temperature,
Surrounding
Body
humidity, dust content,
conditions
harmful gas, etc.
Input/
If input, output voltage
output
Voltage
is abnormal
terminal
If the fastenings come
loose, if any signs
show overheat,
Overall conditions
discharging, or too
high dust content, or
the air piping is
blocked
Main
Electrolytic
If there is abnormal
circuit
capacitance
appearance
Current-conducting
If the parts come
leads or blocks
loose
If the screws or bolts
Terminals
come loose
"D" means daily check and "R" means regularly check.
"√" means need daily check or regularly check
For inspection, do not disassemble or shake the parts without reason, and
still less pull off the plug-in-parts at random. Otherwise, the unit will not
operate normally, or can not enter the mode of fault display, or causes faults
of components or even parts of the main switch components IGBT module
Check to be done
Method
As per use
Visual check
No abnormal
Visual and audible
check
Check visually, by
smelling and
Section 2-1
feeling
Measure at
As per standard
R, S, T and U, V,
specifications
W terminals
Check visually,
tighten the
No abnormal
fastenings, and
conditions
clean the related
parts
No abnormal
Check visually
No abnormal
Check visually
Tighten the loose
No abnormal
screws or bolts
73
Section IX. Maintenance
is damaged.
If measuring is necessary, the user should note that much different results
will be gained possibly if the measuring is performed with different
instruments. It is recommended that the input voltage be measured with
pointer-type voltmeter, output voltage with rectification voltmeter, input and
output current with tong-test ammeter, and power with electrically-driven
wattmeter.
9-2. Periodically-Replaced Parts
Criterion
In order to ensure the operation reliability of the frequency converter, in
addition to regular maintenance and inspection, all the parts suffering
long-term mechanical wear should be replaced at a regular interval, which
state
includes all cooling fans and the filtering capacitors of main circuits for
energy buffer and interchange and PCBs. For continuous use under normal
sound or
conditions, these parts can be replaced according to the following table and
vibration
the operating environment, loads and the current state of frequency
converter.
As per
Part name
Cooling fan
Filtering capacitor
PCB (printed circuit board)
9-3. Storage
The following actions must be taken if the frequency converter is not put into
use immediately after delivery to the user and need to keep well for the time
being or stored for a long time:
condition
Stored in a dry and adequately-ventilated place without dust and metal
powder at the temperature specified in the specifications.
condition
If the frequency converter is not put into use after one year, a charge
test should be made, so as to resume the performance of the filtering
condition
capacitor of main circuit in it. For charging, a voltage regulator should
be used to slowly increase the input voltage of the frequency converter
until it reaches the rating, and the charge should last more than 1~2
hours. This test should be made at least once a year.
Don't perform breakdown test at random, for this test will cause shorter
life of the frequency converter. The insulation test must be performed
after the insulation resistance is measured with a 500-volt mega ohm
and this value must not be less than 4MΩ.
Interval for replacement
1~3 years
4~5 years
5~8 years
74