RUN/ STOP
FWD (running in closed state;
stop in open state)
FWD/ REV
REV (running forward in closed state;
running reverse in open state)
COM
e.g.: 3-point running control
STOP
RUN
FWD (running in closed state)
(stop in open state)
STOP
FWD/ REV
(running forward in open state;
REV
running reverse in closed state)
COM
MSS terminal distribution:
F62 terminal control mode Value STOP terminal
3-point running control 1
2
3-point running control 2
3
3-point running control 3
4
Note: When terminal running control select 3-point running control (F62=2),
if. F63 is1 or 2, SS1/SS2 executes 3-step speed/acceleration running, SS3
is only for 3-point running control; if.F63 is 3, SS3 is for jog reverse control
in priority.
F63: MSS terminal function selection
This parameter can control MSS multi-step speed or MSS multi-step
acceleration.
0: Invalid.
1: MSS multi-step speed control. It is valid only when F04=0/1/2/3,
multi-step speed in priority.
Level triggers, valid in low level.
2: MSS multi-step acceleration control. It is valid only when F04=0/1/2/3/8.
Level triggers, valid in low level.
3: Jog forward/reverse control.
Jog reverse running with SS3 and COM short circuited, Jog forward
Section VI. Function Parameter Description
F63=1/2
F63=3
SS1 and SS2
Jog reverse
SS3
realize speed
invalid
3/acceleration
Multi-speed
SS2
SS3 jog reverse
/acceleration invalid
Multi-speed
SS1
SS3 job reverse
/acceleration invalid
factory setting: 0
51
Section VI. Function Parameter Description
running with JOG and COM short circuited, previous set JOG direction is
invalid.
Level triggers, valid in low level.
Note: F62=2 Terminal control mode is 3-point running control, SS3 is for
jog forward/reverse control in priority.
4: Frequency setting mode switch
OFF when SS1, SS2, SS3 open to COM; ON when SS1,SS2,SS3 short
circuited to COM.
SS3
SS2
SS1
OFF
OFF
OFF
Program running (F04=5) Run at spped 1(F51=0)
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Program running(F04=5) Running at the speed before
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
*5: Reserved
6: MSS time running function.
Running time is set by MSS terminal pulse signal. Running time is refreshed
with the last terminal pulse signal, and is not cumulative. running time
includes accelerate time, barring decelerate time. PRI is SS3>SS2>SS1.
Running parameter
Keyboard and RS485
V2
I2
V2+I2
F04
Keypad potentionmeter
V2 Forward/Reverse
Keypad
potentionmeter
FWD/REV
Accelerate/decelerate time
Running time
Frequency setting mode switch
I2 (F04=2)
V2(F04=1)
*Reserved
stop(F51=1)
V2+I2(F04=3)
Keyboard
Keyboard petentionmeter
SS1
SS2
0
H00
H01
1
V2
V2
2
I2
I2
3
V2+I2
V2+I2
8
Keypad potentionmeter setting
9
V2 Forward/Reverse setting
10
Keypad potentionmeter setting
H14/H15
H16/H17
H07
H08
52
SS3
H02
V2
I2
V2+I2
H18/H19
H09