F57: Percentage in energy saving running
output voltatge (V)
100%
75%
This parameter is for minimum output voltage percentage in energy saving
running For constant torque running, inverter can calculate the optimized
output voltage to the load according to the load state. Calculation is invalid
during acceleration or deceleration. This function is to save energy by lower
the output voltage and enhance the frequency factors, this parameter
confirms the minimum reduced output voltage; if the parameter is set 100%,
the energy saving running mode is closed.
If energy saving is effective, inverter's actual voltage output value=inverter's
rated output voltage × output voltage percentage × energy saving output
voltage percentage.
F58: FDT frequency set 1
F59: FDT frequency set 2
output frequency
FDT1=35Hz
FDT2=30Hz
FDT frequency
OFF
ON
setting 1 arrived
FDT frequency
OFF
ON
level detect
ON express signal action; OFF express no signal action
When output signal select(o13-o17) 14, inverter's output frequency
arrives or accesses FDT frequency set 1, output signal terminal actions;
inverter's output frequency is lower than the set frequency, output signal
does not action.
When output signal select(o13-o17) 15,firstly FDT frequency set 1
inspected, inverter's output frequency arrives or accesses FDT frequency
Section VI. Function Parameter Description
factory setting: 100%
frequency (Hz)
factory setting: 0.00/0.0Hz
factory setting:0.00/0.0Hz
time
OFF
O N
time
OFF
ON
time
49
Section VI. Function Parameter Description
set 1, output signal terminal actions; after terminal action, FDT frequency
set 2 inspected, inverter's output frequency is lower than FDT frequency
set 2, output signal terminal does not action.
e.g. FDT frequency set 1 is 35Hz, FDT frequency set 2 is 30Hz, output
signal terminal actions as above:
F60: Frequency inspection range
This parameter defines frequency inspection range for adjusting I/O output
function: 11 set frequency reaching the inspection range.
F61: Load type
The parameter defines the load type, the system automatically adjust the
parameters according to the load type to satisfy different requirement of
different load. Please inquir Powtran technician to select the right load type.
Wrong load type may damage the equipment.
0: general
1: pump
2: Blower fan
3: Plastic jetting mould machine
4: Braiding machine
5: Hoister
6: Pumping jack
7: Belt conveyor
*8~14: Reserved
F62: Terminal control modes
0: standard running control
1: 2-point running control
2: 3-point running control
e.g.: Standard running control
FWD (edge trigger: forward in falling edge,
FWD/ STOP
level trigger: forward in closed state,
REV/ STOP
REV (edge trigger: reverse in falling edge,
level trigger: reverse in closed state,
COM
e.g.: 2-point running control
factory setting: 0.00/0.0Hz
factory setting: 0
factory setting: 0
and stop in rising edge
and stop in open state)
and stop in rising edge
and stop in open state)
50