Setting
Relay Operation Description
Run / Stop
1
At Speed / Stop
2
At Speed / End of Decel
3
Start / End of Decel
4
Short SCR Trip
5
Phase Loss Trip
6
Shunt Trip
7
OL Trip
8
OT Trip
9
Short Circuit Trip
10
Current Imbalance Trip
11
Over Current Trip
12
Under Current Trip
13
Ground Fault Trip
14
Phase Rotation Trip
15
Voltage Imbalance Trip
16
*Note: Flash rate for Setting #23 is ½ second On and Off
Table 5.6.9: Output Relay Programming
TE2 Series Digital Solid State Soft Starter User Manual

5.6.10 Output Relays

There are three programmable relays (rated 240VAC, 5A, 1200 VA) in
the TE2 Series. They can be programmed for change of state indication
for any one of the 32 conditions identified in the following chart.
F060 = Aux Relay 1: Form C (SPDT)
Factory Setting = 1 (Run / Stop)
Range = 1 - 32 (See list)
Use to program the desired operation for Relay # 1.
F061 = Aux Relay 2: Form C (SPDT)
Factory Setting = 2 (At Speed / Stop)
Range = 1 - 32 (See list)
Use to program the desired operation for Relay # 2.
F062 = Aux Relay 3: Form A (SPST, N.O.)
Factory Setting = 22 (Any Trip, 5 - 15)
Range = 1 - 32 (See list)
Use to program the desired operation for Relay # 3.
F063 = Aux Relay Delay Timer for Settings 28 - 31
Factory Setting = 0 (Disabled)
Range = 1 - 999 seconds, or 0 (Disabled)
Use to program the desired On Delay for any Aux. Relay that
has been programmed for Settings 28 through 31 from the chart
below.
Setting
Relay Operation Description
17
Over Voltage Trip
18
Under Voltage Trip During Start
19
Under Voltage Trip During Run
20
Power Factor Trip
21
Power Trip
22
Any Trip
23
Any Trip, flashing output
24
Coast Down Time Lockout
25
Starts Per Hour Lockout
26
Time Between Starts Lockout
27
Any Lockout
28
Run / Stop with On-delay from F063
29
At Speed / Stop with On-delay from F063
30
At Speed / End of Decel with On-delay from F063
31
Start / End of Decel with On-delay from F063
32
Power Loss (nCP No Control Power) Trip
F064 = Reserved
54 |