TE Series Digital Solid State Soft Starters 18 – 1250A
5.6.9

Output Relays

There are three programmable relays (rated 240VAC, 5A, 1200 VA) in
the TE Series. They can be programmed for change of state indication
for any one of the 25 conditions identified in the following chart.
F060 = Aux Relay 1: Form C (SPDT)
Factory Setting = 1 (Run / Stop)
Range = 1 - 27 (See list)
Use to program the desired operation for Relay # 1.
F061 = Aux Relay 2: Form C (SPDT)
Factory Setting = 2 (At-Speed / Stop)
Range = 1 - 27 (See list)
Use to program the desired operation for Relay # 2.
F062 = Aux Relay 3: Form A (SPST, N.O.)
Factory Setting = 16 (Any Trip, 5 - 15)
Range = 1 - 27 (See list)
Use to program the desired operation for Relay # 3.
F063 = Aux Relay Delay Timer for Settings 23 – 26
Factory Setting = 0 (Disabled)
Range = 1 – 999 seconds, or 0 (Disabled)
Use to program the desired On Delay for any Aux. Relay that
has been programmed for Settings 23 through 26 from the chart
below.
Setting
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
Table 5.6.9: Output Relay Programming
F064 = Reserved
Relay Operation Description
Run / Stop (Changes on Start Command, resets on Stop)
At-Speed / Stop
At-Speed / End of Decel
Start / End of Decel
Short SCR Trip
Phase Loss Trip
Shunt Trip
OL (Motor Thermal Overload) Trip
OT (Starter Thermal Over Temperature) Trip
Short Circuit Trip
Current Imbalance Trip
Over Current (Shear-Pin) Trip
Under Current Trip
Ground Fault Trip
Phase Rotation Trip
Any Trip (#5 - #15)
Any Trip, (#5-#15) flashing output*
Coast Down Time Lockout
Starts Per Hour Lockout
Time Between Starts Lockout
Any Lockout (#18-#20)
Run Timer (F030) Engaged
Run / Stop with On-delay from F063
At-Speed / Stop with On-delay from F063
At-Speed / End of Decel with On-delay from F063
Start / End of Decel with On-delay from F063
Power Loss (nCP No Control Power) Trip
*Note: Flash rate for Setting #17 is ½ second On and Off