Chapter 6 - Start-up

F001
F002
F003
F004
F005
F010
F011
F013
F014
F015 - F018
F019 - F028
F029 - F052
F053 - F059
F060
F061
F062
F063
F065 - F068
F070
F071
F073 - F080
F085 - F093
Table 6.1.2: Factory Presets
TE2 Series Digital Solid State Soft Starter User Manual
6.1
Your new TE2 Series Soft Starter is factory preset for a wide variety of
applications and often can be used with minimal adjustment.
6.1.1
6.1.2
Fn #
Motor Nameplate FLA.
Motor Nameplate
Service Factor
Overload Class During Start
Overload Class During Run
Overload Reset
Ramp Profile
Initial Torque
Ramp Time
Current Limit
Ramp 2 settings
Specialty starting and testing
Software protection and control
Timer and counter value readouts
Aux Relay #1
Aux Relay #2
Aux Relay #3
Aux Relay Delay
Communications
Parameter Lock
Reset Function
System settings and time clock
Fault History

Basic Startup

Three Step Process
1. Connect L1, L2, and L3 to the input voltage source and
T1, T2, and T3 to motor.
2. Connect control wires and control power.
3. Program motor FLA (F001).
Start-up Parameters and Factory Defaults
In the initial start-up test, the performance of the starter with the
initial factory presets. If required, adjust or enable the features
to meet your specific application requirements.
Function
Name
Factory
Description / Factory Setting
Setting
FLA must be programmed for
0
the starter to operate.
Change only if necessary and for
1.0 SF
motors rated above 1.0SF
Class 10
NEMA / UL Class 10
Class 10
NEMA / UL Class 10
0 (Manual)
0 = Manual
Ramp 1 and Ramp 2 =
1
Voltage Ramp with Current Limit
60
60% Initial Voltage
10
10 Second Ramp (Ramp 1)
350
350% of programmed FLA
Inactive unless Ramp 2 Input is
---
closed
---
Inactive unless selected
126
Inactive unless selected
---
Read only
1
Run / Stop
2
At-Speed / Stop
16
Any Fault
0
No Delay
Not Used unless without optional
----
Comm Adaptor.
0
User password disabled
0
Use to reset to default values
---
User choice to adjust clock
---
Read only
65 |
P a g e