Appendix 4 (cont.) External OL Relay Applications
Disconnect
R /
L1
U /
T1
MTR
TE2 Series Digital Solid State Soft Starter User Manual
SPECIAL MOTOR APPLICATIONS
Multiple Motors
When more than one motor is connected downstream from the TE2
Series starter, the internal electronic overload protection cannot provide
proper protection of the individual motors. Codes require the use of
separate OLRs for each motor, which would need to be external
devices.
In these instances the TE2 Series Overload protection should be turned
off, deferring protection to the separate OLRs. Care should be taken to
ensure that the External OLR is properly wired into the starter control
circuit to facilitate shutdown of the motor.
or
Circuit
Breaker
TE Starter
S /
T /
L2
L3
Solid State
.
Over Load
.
Bypass
Contactor
"BP"
V /
W /
T2
T3
G
External
Over Load 1
1
120VAC CONTROL POWER
Start / Run
.
Command
1
2
3
TE2 -TB-1
(24VDC)
External
Over Load 2
MTR
2
A1
A2
TE2 -TB-2
External
External
OL 1
OL 2
4
5
TE2 -TB-1
(NC Input )
TE2 ...-BP Series
Control Wiring