The Te2 Function List - Toshiba TE2 Series Instruction Manual

Low voltage digital solid state soft starter
Table of Contents

Advertisement

Fn #
Group
Function Description
Motor Nameplate FLA
F001
FLA must be programmed for
starter to function.
Motor Nameplate
F002
Service Factor
F003
Overload Class During Start
F004
Overload Class During Run
F005
Overload Reset
F006
-
Reserved for factory use
F009
Table 5.5.1: Motor and Overload Function Group
Fn #
Group
Function Description
Ramp Type Selection:
F010
VR = Voltage Ramp
CR = Current PID Ramp
1 = Ramp 1, 2 = Ramp 2
Table 5.5.2: Starting Mode Function Group
TE2 Series Digital Solid State Soft Starter User Manual
5.5

The TE2 Function List

5.5.1
Motor FLA, Service Factor and Overload Protection
Functions
Adjustment / Display Range
50 -100% of Max Amp Rating.
Upper limit of range automatically
adjusts downward as Service factor
is increased.
1.00 - 1.30 SF
NEMA / UL Class 5 -30
NEMA / UL Class 5 - 30
0 = Manual
1 = Auto
2 = Disabled Overload
5.5.2
Starting Mode Functions
Adjustment / Display Range
Setting 1 = VR1 + VR2
Setting 2 = CR1 + CR2
Setting 3 = VR1 + CR2
Setting 4 = CR1 + VR2
0 - 100% Line Voltage
0 - 600% Motor Current
1 - 120 seconds
200 - 600% Motor Current
0 - 100% Line Voltage
0 - 600% Motor Current
1 - 120 seconds
200 - 600% Motor Current
Setting
Factory
Increments
Setting
1 amp
0
0.05
1.0 SF
5
Class 10
5
Class 10
0
1
(Manual)
Setting
Factory
Increments
Setting
1
1
VR1+VR2
1%
60%
1%
200%
10
seconds
1%
350%
1%
60%
1%
200%
10
1 second
seconds
1%
350%
30 |
P a g e
Section
5.6.1
and
3.2
Section
5.6.2
and
Append.
1
5.6.2,
Append.
1
and
4.2.5

Hide quick links:

Advertisement

Table of Contents
loading