Sizes And Ratings - Toshiba TE2 Series Instruction Manual

Low voltage digital solid state soft starter
Table of Contents

Advertisement

Table 1.2 TE2 Series Range
Model
Number
Min.- Max.
TE2-18-BP
TE2-28-BP
TE2-39-BP
TE2-48-BP
TE2-62-BP
TE2-78-BP
TE2-92-BP
TE2-112-BP
TE2-150-BP
TE2-160-BP
TE2-210-BP
105 - 210
TE2-275-BP
138 - 275
TE2-361-BP
181 - 361
TE2-450-BP
225 - 450
TE2-550-BP
275 - 550
TE2-600-BP
300 - 600
TE2-862-BP
431 - 862
TE2-900-BP
450 - 900
TE2-1006-BP
503 - 1006
TE2-1250-BP
625 - 1250
TE2 Series Digital Solid State Soft Starter User Manual
1.2

Sizes and Ratings

The Toshiba TE2 Series starters are current rated controllers. Max.
Amp ratings are for continuous duty and must not be exceeded. Always
check the motor nameplate FLA and Service Factor to ensure proper
sizing.
Each size has an adjustable current range of 50% to 100% of the Max
Amp rating. Table 1.2 shows the Current Ratings available.
1.2.1
Many NEMA design motors include a design rating referred to
Current
as Service Factor (SF) that may allow continuous operation
Range
above the nameplate current rating. If using this Service
Factor, the TE2 Series starter must be sized for the total amps
used. For proper selection of the TE2 Series starter when
using SF continuously, multiply the nameplate FLA by the
9 - 18
stated Service Factor, or use stated Service Factor Amps
14 - 28
(SFA) if listed on the nameplate. The following excerpt is from
19 - 39
the NEMA MG-1 standards for AC Motors that describes the
issues concerning the use of Service Factor ratings.
24 - 48
36 - 62
"When an induction motor is operated at any service factor
39 - 78
greater than 1.0, it may have efficiency, power factor and
speed different than those at rated load. Locked rotor torque
46 - 92
and current and breakdown torque will remain the same. A
56 - 112
motor operating continuously at any service factor greater than
1.0 will have a reduced life expectancy compared to operating
75 - 150
at its nameplate horsepower."
80 - 160
When using this feature, simply program the TE2 Series
Service Factor (F002) to the nameplate rating. (See section
5.6.1.) All other adjustments to the protection circuits are done
automatically within the TE2 Series.
1.2.2
If you need to be able to start the motor Across-the-Line when
the TE2 Series electronics are out of service, the starter can
also be selected based upon the rating of the Bypass
Contactor. Some users may also elect to size their Bypass
Contactors per NEMA guidelines. When doing this, please
refer to the Product Selection Guide for details and notes, and
see Appendix 4 for special considerations regarding Overload
Protection.
1.2.3 The TE2...-BP Series starters include the ability to connect a
dry contact directly to the Bypass Contactor coil control circuit.
These terminals are covered when shipped and should be used
ONLY when necessary for Emergency Bypass operation and with
an external Overload Relay. See Appendix 4 for additional
information.
No field wiring to these terminals is necessary if this feature is not
used.
Selecting for Service Factor Utilization
Selecting for Across the Line Bypass
4 |
P a g e

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents