F052
Fault Condition
Setting
Description
0
Auto Reset Disabled
1
Over Temperature Trip
Over Current (Shear
2
Pin) Trip
3
Under Current Trip
4
Phase Loss Trip
5
Current Unbalance Trip
6
Ground Fault Trip
7
Short Circuit Trip
8
Voltage Imbalance
Note 1: UC, OC or UB require operation to resume before the fault can be detected.
Note 2: Cycling and / or restoration of control power will reset all of the above faults.
Note 3: Overload Trip reset function is programmed only in F005. See Section 3 for details
Note 4: Reset attempts with a fault condition present will cause a new fault. This will be logged into the fault history (F085 - F093) and may
overwrite previous fault records.
Table 5.6.8.b: Faults Selected for Auto-Restart
TE2 Series Digital Solid State Soft Starter User Manual
F052 = Auto-Reset Selected Faults
Factory Setting = 4 (Phase Loss)
Range = 1 - 17, or 0 (Disabled)
If F052 = 1 through 17, the TE2 Series will attempt to restart
after the fault(s) coded in the following table. Only one selection
can be entered.
Display
F052
Readout
Setting
Reference
---
10
OT
11
OC
12
13
UC
PL
14
IB
15
GF
16
SC
17
EI
F053 = Auto-Restart Attempts
Factory Setting = 0 (Disabled)
Range = 1 - 10 Attempts, or 0 (Disabled)
If F053 = 1 through 10, the TE2 Series will attempt to restart if
the Start Command is present for this number of times. If set to
Zero, the starter will NOT attempt to reset automatically.
Fault Condition
Description
Under Voltage
Power Factor
PoweR (KW)
Any fault #1-3 above
Any fault #4-6 above
Any fault except #7
Any fault except #6 & #7
Any fault
52 |
P a g e
Display
Readout
Reference
UE
PF
PR