Badger Meter FC-5000 User Manual page 42

Industrial flow computer
Hide thumbs Also See for FC-5000:
Table of Contents

Advertisement

Advanced Setup
Oelay OutputsE: Oelay Mode
Use this menu to change the mode of one or both relay outputs� The mode
defines the behavior of the output�
1� Navigate to SETUP > ADVANCED SETUP > RELAY OUTPUTS.
2� Press UP/DOWN to scroll to an output mode, then press ENTEO�
3� Scroll through the available modes, then press ENTEO to select and save
the setting�
Option
NO RELAY/DISABLED
TOTALIZER
ALARM: HIGH
ALARM: LOW
ALARM: RANGE
MANUAL
Oelay OutputsE: Oelay Settings
Use this menu to change the relay settings for the respective relay mode�
1� Navigate to SETUP > ADVANCED SETUP > RELAY OUTPUTS�
2� Press UP/DOWN to scroll to the applicable relay setting, then press ENTEO�
3� Scroll to and edit each option, as necessary�
N
OTEE:
Alarm icons "R1" and "R2" will appear in the upper right section of the
Home Screen to provide a local indication when a relay condition has been
met and when the relay has be energized�
Output Mode Option
OUTPUT SOURCE Parameter assignment (e�g� Flow Total or Mass Total)
SCALING FACTOR Pulse(s) transmitted per unit of measure
TOTALIZER
UNITS
PULSE WIDTH
OUTPUT SOURCE Parameter assignment (such as Flow Rate or Temperature)
HIGH SETPOINT
HYSTERESIS HI
ALARM: HIGH
SET DELAY
RELEASE DELAY
LATCHING
Page 42
Description
Disables output
Totalizer output
On/Off function, energized at the high set point
On/Off function, energized at the low set point
On/Off function, energized beyond high and low set points
On/Off function of manual operation
Table 29: Relay mode options
Description
Converts output unit of measure
Time between the rising and falling edges of a single pulse
Instructs the device to energize the relay if this value reached/
exceeded� This value is linked to the OUTPUT SOURCE and its unit
of measure (for example, Flow Rate in GPM)
Creates a window/zone below the HIGH SETPOINT value where
the relay remains in an energized state
Time in seconds that will elapse before the relay energizes, if the
HIGH SETPOINT value is reached/exceeded
Time in seconds that the relay will remain energized, if the
HYSTERESIS HI value is reached/exceeded
Leaves the relay in an energized state until it is manually cleared
on the device, either through the keypad interface or through
the Digital I/O channels