Start-Up
4.3
Starting up the PLC
Sub–range 2 can be used to analyze the active alarm responses.
Sub–range 1 can only be read or written as a double word. Sub–range 2 can only be read.
You can delete self–clearing alarms by resetting the respective bit in the variable range
''1600xxxx'' in sub–range 0 (1 –> 0 edge).
The remaining user alarms are cleared by the PLC after detecting the respective cancel condi-
tion. If the alarm is still present, the alarm occurs again.
User alarm activation
Alarm handler
Feed disable active
User program
Example:
Feed disable=0
User alarm with feed
disable
Alarm handler
Module:
Analyze user alarm
Fig. 4-2
Configuring user alarms
Each alarm is assigned a configuration byte. The user alarms can be configured by the user in
machine data 14516_MN_USER_DATA_PLC_ALARM.
Default setting MD 14516: 0 => SHOW ALARM/SELF–CLEARING user alarm
Configuration byte structure:
S
Bit0 – bit5 :
S
Bit6 – bit7 :
4-62
User
Int.
interface
inter–
face
PLC cycle
User alarm with Feed Disable alarm response
Alarm responses
Cancel criterion
Feed disable in the NCK is
active for all axes as long as the
PLC user alarm is active.
6FC5 597–2AA00–0BP2 (01.02)
SINUMERIK 802S