Data Aire Mini dap4 Installation, Operation & Maintenance Manual page 58

Table of Contents

Advertisement

iii)
If the High CO
high CO
alarm set point, a "High CO
2
will sound (if not programmed for Silence). This alarm is a warning only and will not
prevent any of the unit functions from operating. The alarm will remain until the alarm
condition is corrected. The alarm output contacts will close if this alarm is selected "Yes"
in the alarm output function list in menu K.
iv)
If the Low CO
low CO
alarm set point, a "Low CO
2
will sound (if not programmed for Silence). The alarm is a warning only and will not
prevent any of the unit functions from operating. The alarm will remain until the alarm
condition is corrected. The alarm output contacts will close if this alarm is selected "Yes"
in the alarm output function list in menu K.
v)
CO
2
setting), CO
normal control mode during day schedule or light is on.
b)
Night time mode
i)
The night mode can be activated by either; an optional light sensor input or by a
programmed time schedule.
ii)
While in the night mode, the temperature and humidity set points will be offset by
the amount of their offset band settings. See section 3c for details.
iii)
A "Night Sch" status message will appear and the offset Temperature ("TSP") and
offset Dehumidify ("HSP") set points are displayed instead of the normal set points.
iv)
Set point offsets work as follows:
Normal daytime mode
Cooling and Heating Temp set point = Temp set point
Humidify and Dehumidify set point = Hum set point
Temp and Hum set points are adjusted in menu B "Set point".
Nighttime mode
Cooling Temp set point = Temp set point + Cooling offset
Heating Temp set point = Temp set point - Heating offset
Humidify set point = Hum set point - Humidify offset
Dehumidify set point = Hum set point + Dehumidify offset
Night time offsets are adjusted in menu C "Clock/Scheduler".
v)
CO
2
"No" (default setting) in Menu J "Factory settings". CO
daytime mode.
58 • Mini dap4 User Manual
level alarm is enabled (Yes) and the CO
2
level alarm is enabled (Yes) and the CO
2
control during Day/Night schedule: If night CO
control will be off at night or when light sensor senses no light and back to
2
control can be disabled during the nighttime by setting "Night CO
level" message is displayed and audio alarm
2
level" message is displayed and audio alarm
2
control will resume during
2
level rises above the
2
level drops below the
2
control is set to No (default
2
cntrl" to
2