Engy Svg Cool
Aux Chill Wtr
Chill Wtr Reg
Available Selections:
Wtr Vlv Voltage: 0 to 10, 2 to 10, 7 to 10, 6 to 9, and 4 to 7
Wtr Vlv Action: Direct or Reverse
Engy Lockout Time: 15, 30, 45 and 60m
Once a selection or selections have been made, move the cursor to the title block by pressing the ENTER key
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
26 • Mini dap4 User Manual
Water Valve Settings
Wtr Vlv:
Engy Svg Cool
E-Saver Assist:
none
Wtr Vlv Voltage:
2-10*
Wtr Vlv Action:
Direct*
Engy Lockout Time:
15m*
Water Valve Settings
Wtr Vlv:
Aux Chill Wtr
E-Saver Assist:
none
Wtr Vlv Voltage:
2-10*
Wtr Vlv Action:
Direct*
Engy Lockout Time:
15m*
Water Valve Settings
Wtr Vlv:
Chill Wtr Reg
Discharge Temp Is Required
Wtr Vlv Voltage:
2-10*
Wtr Vlv Action:
Direct*
Engy Lockout Time:
15m*
Humidity Settings
Control:
Rel. Hum
Humidify: Compu Non-Mod
Dsat Cyc:
Not Used
Hum Anticipation:
Off
Dehum Mode:
None