See Logic section for Relative humidity and Dewpoint control for details.
Available Selections:
Humidify:
Dsat Cyc:
Hum Anticipation: On or Off
Dehum Mode:
Once a selection or selections have been made, move the cursor to the title block by pressing the ENTER key or
press the ESC key to return normal operating mode
▼ Press the DOWN key to view the next screen.
The following will be displayed (values are for reference only):
Note: Selecting YES will reset all values back to the factory settings (default).
If YES is selected, the following message will be displayed: "wait resetting" (resetting will take a few seconds). Once
set the display will have the following message:
Power down the unit using the unit mounted electrical disconnect or the (field provided) wall mounted disconnect.
Once the self-test is complete, the display module will display that the unit is "OFFbyKEY"
Start (power-up) the unit following the instructions on page 7, Powering the Unit ON/OFF.
27 • Mini dap4 User Manual
Compu Non-Mod (Computer Room, Non-Modulating)
Computer Mod (Computer Room, Modulating)
Comf Non-Mod (Comfort, Non-Modulating)
Comf Mod (Comfort, Modulating)
None
Not Used or 1, 2, 3, 4 or 5 M Off (Minutes)
None
1C In Limit (1 compressor & within reheat limits)
2C In Limit (2 compressors & within reheat limits)
1C No Limit (1 compressor & no reheat limits)
2C No Limit (2 compressors & no reheat limits)
Settings Management
Clear user settings
and replace them with
factory defaults? NO
Warning
INITIALIZATION DONE
switch-off unit
to confirm data