5.7 Master copies
5.7.1.12

Counted value typicals Cnt01D_S / Cnt04D_S

Function
● Cnt01D_S: Send 1 counted value (32 bits).
● Cnt04D_S: Send 4 counted values (32 bits).
Note that the parameter "DifferenceValue" for forming the difference value can only be
activated at the same time for all four counted values.
Parameter
Parameter:
Parameter:
Declaration:
Data type:
Range of
values:
Default:
Explanation: Restore collective command
176
PartnerNo
PartnerObjectNo
Enabled
ImageMemory
Conditional
Unconditional
TimeStamp
For a description, see section Reoccurring parameters (Page 144).
GeneralTriggerCommand
INPUT
BOOL
TRUE / FALSE
FALSE
The restore collective command as a central system memory bit belongs to
the organizational SINAUT system commands.
Set the parameter to TRUE if the counted value transfer is to be triggered by a
restore collective command.
• When the destination subscriber no. (PartnerNo) = 0 (transfer to all), the
restore collective command is taken into account.
When the restore collective command is detected, the currently
accumulated counted value is transferred regardless of other triggers for
transfer. The restore bit is inverted in this counted value.
• If in the typical an explicit destination subscriber no. (PartnerNo > 0) is
configured, the restore collective command is evaluated in the
corresponding subscriber object in the central administration.
You can use the parameters "GeneralTriggerCommand" and "TriggerInput" at
the same time. In this case the transfer is triggered both by an edge change
0 → 1 at "TriggerInput" and when a restore collective command is received.