Automatic star delta starter

Advertisement

Quick Links

s
Automatic Star Delta
Starter 3TE7291-0A
For dependable service, it is of utmost
importance that instructions given below are
followed for selection, inspection, installation,
commissioning, operation and maintenance.
ASD-11 Starter (Self reset)
Selection of Starter
• Refer Table A for recommended selection of 3TE72
starters.
Table A: kW/HP Rating, thermal overload relay range &
fuse rating, Coil Voltage, Maximum full load current for
different types of motors.
6
7
Fig. 1: ASD-11 Starter
Installation:
• Remove the front cover.
• Mount the starter on a vertical wall/ plate free from
vibrations with proper nuts and bolts. Refer Fig. 8 for
mounting dimensions and Fig. 4 for permissible mounting
position.
• Remove the rubber grommets for the incoming and
outgoing cable connections.
• Connect incoming and outgoing cables as follows (Refer
Fig. 2 & 3):
– Use proper cable glands to ensure dust proofing. For
conduit entry use packed washers.
– Select correct size of cables from Table-A
– Connect line and motor leads exactly as per wiring
diagram pasted inside the cover of the starter.
– Terminate the incoming cable on terminal block.
Installation, Operation & Maintenance
Instructions
Please read and understand these instructions before
installating, operating, or maintaining the equipment. Keep for
future reference
Danger
Hazardous voltage can cause death or serious injury. Disconnect
power before working on equipment.
Warning
Automatic Motor Restart.
Can cause death, serious injury or property damage.
Do not use automatic reset mode when unexpected automatic
restart of the motor can cause injury to persons or damage to
equipment.
Reliable functioning of the equipment is only ensured with
certified components. Commissioning and maintenance by
qualified personnel only.
NOTICE
This product has been designed for environment A. Use of this product
in environment B may cause unwanted electromagnetic disturbances in
which case the user may require to take adequate mitigation measures.
IS/IEC 60947-4-1
4
1. ON Push Button
8
2. OFF Push Button
3. Earthing Screws
4. Rubber Grommet (Not visible in Fig 1.)
1
5. Name Plate
6. Incoming Cable
2
7. Outgoing Cable
8. Cover Fixing Screws
9
9. Mechanical Latch (OFF push button) to be used for
preventing undesired ON operation of Starter
3
5
– Connect outgoing cables on the Relay (K1) terminals
and Delta contactor (Q3) terminals.
Tightening torque (N-cm):
kW Ratings
7.5 – 11
15 – 18.5
• Connect the earthing conductor to terminals marked
(earth) on the starter body with torque 80 to 140 N-cm.
The Starter is now ready for commissioning.
• Initially set the overload relay to 0.58 times the rated
motor current.
• Set the timer dial to the nearest value of starting time
available on motor name plate
• If it is not available then set the dial to approximately
6-8 secs.
Incoming Terminals
Outgoing Terminals
80 – 140
80 – 140
150 – 210
100 – 150

Advertisement

loading

Summary of Contents for Siemens TE7291-0A Series

  • Page 1 Installation, Operation & Maintenance Instructions Automatic Star Delta Please read and understand these instructions before installating, operating, or maintaining the equipment. Keep for future reference Starter 3TE7291-0A Danger Hazardous voltage can cause death or serious injury. Disconnect For dependable service, it is of utmost power before working on equipment. importance that instructions given below are Warning followed for selection, inspection, installation, Automatic Motor Restart. Can cause death, serious injury or property damage. commissioning, operation and maintenance.
  • Page 2 0.58 times the rated current on the motor name – Overload relay characteristics shown in Fig. 6 can be plate. used to estimate the average tripping time at different • If the relay trips even when set at rated motor current, multiples of set current. the suitability of the starter/relay for the particular – In the absence of an ammeter, use the procedure given application should be checked with the nearest below: Siemens office.
  • Page 3 Operating Characteristics: same. The tripping times of the same. The tripping times shown are for relays starting from the cold state. At operating The given characteristics (Fig. 6) are average values of all temperatures (heated at rated current) these are reduced to ranges and sizes of bimetal relays and are mainly intended about 25% of the value obtained from the characteristics. to indicate the inverse time current characteristics of the Fig. 6: Operating characteristics of 3UW51/52 relays Operation: • Replacement of Overload Relay (Refer Fig. 7): • Rotate the Latch away from OFF push button – Removal • For starting the motor, press Green push button marked ‘I’ 1. Disconnect the wires connected to the relay terminals. (Fig. 1) 2. Slightly loosen the outgoing terminal screws of the line • For stopping the motor press Red push button marked ‘O’ contactor. (Fig. 1) 3. Follow instructions given in Fig. 7 for removal of relay. • This is in ‘Self-Reset’ mode. In this mode even, if the – Re-fixing relay trips on overload, it will be automatically reset in a 1. Select & take the overload relay of same range.
  • Page 4: Other Tables

    Contactor outgoing terminals Hook on relay for engagement Fig. 7: Contactor – Relay Connection Replacement of coil Table A: Automatic Star - Delta Starter Type Ref: 3TE7291-0A I(fl) Recommended Cu 4 Pole Recommended Recommended Contactor Line Contactor Delta Contactor Star Cable size Motor Squirrel cage Overload relay at 50ºC Fuse Switch Output motor 415V Line Phase Back up Relay...
  • Page 5 Notes...
  • Page 6: Dimensional Drawing

    Dimensional Drawing Automatic Star Delta Starter Mounting Dimensions 259 x 219 and hole Dia 7.0mm Fig. 8: Dimensional Details for 3TE72 91-0A** Disposal Siemens products are environment friendly, which PLASTICS: Segregate as per material type for recycling predominantly consist of recyclable materials. through authorized dealer. Because of the long lifetime of For disposals we recommend disassembling and separation Siemens Products the disposal guidelines may be replaced into following materials: by other national regulations when taking the product out of service. The local customer care service is available at any METALS: Segregate into Ferrous types for recycling through time to answer disposal-related questions. authorized dealer. For more information call us on 1800 209 1800 Email: ics.india@siemens.com Order No. A5E41708219000A-AD SACHIN ENTERPRISE Siemens Ltd. Product development is a continuous process. Consequently the data indicated in this Leaflet is subject to change without prior notice. For latest issue contact our sales offices.