4.16 MSC authentication

Table 4- 4
Byte no.
Table 4- 5
Bit No.
4.16
MSC authentication
MSC authentication on the different interfaces
When using the secure MSC protocol (MSC / MSCsec), the authentication data for the
interfaces involved must be configured for the TIM as MSC station and as MSC node station.
Parameter groups
● MSC authentication - Ethernet interface
Relevant when using MSC on the Ethernet interface X1
● MSC authentication - MD720
Relevant on the serial interface when using MSC via mobile wireless
Parameter
● User name
User name for communication using MSC
● Password
Password for communication using MSC
The user name and password must be different for every MSC station in the network.
90
Assignment of the structure of the time stamp
Content
High nibble
0
Year * 10
1
Month * 10
2
Day * 10
3
Hour * 10
4
Minute * 10
5
Second * 10
6
Millisecond * 100
7
Millisecond * 1
The assignment of the half byte "time status" (low nibble of byte 7)
Value
Meaning
0
0
Time is invalid
1
Time is valid
1
0
Standard time
1
Daylight saving time
2
Not used
Not used
3
Low nibble
Year * 1
Month * 1
Day * 1
Hour * 1
Minute * 1
Second * 1
Millisecond * 10
Time status
Operating Instructions, 02/2018, C79000-G8976-C468-02