Block library TeleControl ST7
5.7 Master copies
Name:
Declaration:
Data type:
Range of val-
ues:
Explanation:
Name:
Declaration:
Data type:
Range of val-
ues:
Explanation:
Name:
Declaration:
Data type:
Range of val-
ues:
Explanation:
216
MaxInputTime
INPUT
INT
• 0
Value for unrequired parameter
• 1 ... 32000
Range of values for monitoring time
Monitoring time in ms for commands and setpoints that are input via hard-
ware.
A monitoring time of at least 30 s is recommended.
If you do not require the parameter, specify 0 (zero).
ResetError
INPUT
BOOL
Input
Memory bit
Data bit
Input for resetting the output GlobalCmdOutputError.
If you do not require the parameter, specify a memory or data bit that always
has signal 0.
InputOK
OUTPUT
BOOL
Output
Memory bit
Data bit
Display of the enabling of hardware commands and setpoints
Has a 1 signal as soon as the current entry was enabled, i.e. when the hard-
ware command or setpoint was entered correctly.
The display bit goes off when the entry is reset, in other words when the
command key is released or the setpoint entry key "EnterInput" input is re-
leased.
If you do not require the parameter, specify a memory or data bit in the
memory area of the local data.
I 0.0 ... I n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
Q 0.0 ... Q n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
Operating Instructions, 02/2018, C79000-G8976-C468-02