A SINAUT subscriber (partner) can only be an ST7 CPU or an ST7cc to which a connection
was configured. TIMs cannot be monitored or controlled by FC PartnerMonitor.
Note
FC PartnerMonitor in a station
FC PartnerMonitor can also be used in a station. However, the control inputs for establishing
and terminating a permanent connection can then no longer be used. This only works in the
master station when the local TIM is a master station TIM.
Parameter
Name:
Declaration:
Data type:
Range of
values:
Explanation
Name:
Declaration:
Data type:
Range of
values:
Explanation
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
PartnerNo
INPUT
INT
1 ... 32000 [ms]
SINAUT subscriber no. of the subscriber to be monitored and controlled.
If the set "PartnerNo" is not found in the administration (DB BasicData), then
(only during startup) an entry is written to the diagnostics buffer (event ID
B101). The CPU does not change to STOP.
The status of a subscriber with correct parameter settings is indicated in the
"PartnerStatus" output word and the control inputs are processed.
An unknown subscriber is not processed until the error is eliminated. The
"PartnerStatus" output word remains set to 0 during this time.
MaxConnectTime
INPUT
INT
• 0 (no limitation)
• 1 ... 480 [minutes]
Maximum duration of a permanent connection
The time specified here (> 0) is activated at the start of a permanent connec-
tion (see "PermanentCall_On" parameter).
If the time elapses before the permanent connection is reset, it is automatical-
ly disconnected. The time is retriggered as long as the signal 1 is present at
the "PermanentCall_On" input.
The time specified here applies to a permanent connection in a dial-up net-
work as well as to a permanent connection (continuous polling) on a dedicated
line.
Block library TeleControl ST7
5.7 Master copies
229