Siemens TIM 1531 IRC Operating Instructions Manual page 217

Telecontrol
Table of Contents

Advertisement

Name:
Declaration:
Data type:
Range of val-
ues:
Explanation:
Name:
Declaration:
Data type:
Range of val-
ues:
Explanation:
TIM 1531 IRC
Operating Instructions, 02/2018, C79000-G8976-C468-02
InputError
OUTPUT
BOOL
Output
Memory bit
Data bit
Display of entry errors with hardware commands and setpoints
The output has a 1 signal when one of the following hardware entry errors is
detected within the monitoring time "MaxInputTime":
• Two or more command and/or setpoint entries were detected at the same
time.
• At one of the inputs a 1 signal was detected over a longer period of time
(for example when the input is defective).
If you do not require the parameter, specify a memory or data bit in the
memory area of the local data.
GlobalCmdOutputError
OUTPUT
BOOL
Output
Memory bit
Data bit
Group message: In a station a command output error was detected.
A command output error can occur at the receive end only in the following
cases:
• The content of the two command bytes in the received frame is not
identical.
• More than one bit is set in the command byte (1-out-of-8 error).
If such an error is detected, this is sent by the station with an organizational
frame to the subscriber that sent the commands. FC Safe on the sending
subscriber then indicates the disruption at the output GlobalCmdOutputError.
When an error is detected, the output remains set to the 1 signal until you
request the group signal to be reset via the "ResetError" input.
If you do not require the parameter, specify a memory or data bit in the
memory area of the local data.
Block library TeleControl ST7
Q 0.0 ... Q n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
Q 0.0 ... Q n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
5.7 Master copies
217