Command Output - Siemens TIM 1531 IRC Operating Instructions Manual

Telecontrol
Table of Contents

Advertisement

Configuration
4.22 Data points
Note
Evaluation of the value even when the option is disabled
If you enable one or both options and configure a value and then disable the option later, the
grayed out value is nevertheless evaluated.
To disable the two options, delete the previously configured values limit values from the input
boxes and then disable the relevant option.
Recommendation for quickly fluctuating analog values:
If the analog value fluctuates quickly, it may be useful to smooth the analog value first if limit
values are configured.
4.22.9

Command output

Parameters for the data point type "Command output (Cmd01B_R)"
The following output options can alternatively be assigned to a data point of the type
"Command output (Cmd01B_R)":
● LATCH_ON/OFF
The function permanently latches the command output to the value 1.
Note:
The latched value is only canceled by a new command. Alternatively, the command can
be reset by the user program.
● PULSE_ON/OFF
The function evaluates the "Command output time" for the command output of the data
point.
Parameter
Name:
Range of val-
ues:
Explanation:
Name:
Range of val-
ues:
Default:
Explanation:
126
Max. number of pulses
1
Only a single received pulse is evaluated. If the number of pulses received
exceeds the value 1, the command is discarded.
Command output time (s)
0 ... 65535
0
Period for which the command is output.
Only for the "PULSE_ON/OFF" option.
When the time expires, the output is automatically reset.
With zero, a set command output is not automatically reset. In this case, you
need to reset the output via the user program.
Operating Instructions, 02/2018, C79000-G8976-C468-02