Block library TeleControl ST7
5.7 Master copies
Processing not enabled
ImageMemory
Parameter:
Declaration:
Data type:
Range of
values:
Default:
Address
range:
Using in typi-
cals
150
• With sending process typicals
(Bin04B_S, Ana04W_S, Cnt01D_S/Cnt04D_S,
Set01W_R, Par12D_R,
Dat12D_S, Dat256D_S)
If processing is not enabled, the block can only communicate at the
organizational level; in other words, Org frames can be sent and received.
Please note: Although a query from an operator typical is answered,
however the reply frame contains the data valid at the time the function
was disabled.
Note
The response described here does not apply to Cmd01B_R, (see
Command typical Cmd01B_R (Page 173))!
• With receiving operator typicals
(Bin04B_R, Ana04W_R, Cnt01D_R/Cnt04D_R,
Set01W_S, Par12D_S,
Dat12D_R, Dat256D_R)
If processing is not enabled, the block can only communicate at the
organizational level; in other words, Org frames can be sent and received.
Please note: A request can still be sent and the answer received, the
received information is, however, not output to the outputs. You will find the
relevant outputs in the description of the appropriate data point typicals.
Note
The response described here does not apply to Cmd01B_S, see
Command typical Cmd01B_S (Page 171)!
ImageMemory
INPUT
BOOL
TRUE / FALSE
TRUE
Input
Memory bit
Data bit
Bin04B_S, Ana04W_S, Cnt01D_S/Cnt04D_S, Set01W_R, Par12D_R,
Dat12D_S, Dat256D_S
I 0.0 ... I n.7
M 0.0 ... M n.7
L 0.0 ... L n.7
DBm.DBX 0.0 ... n.7
Operating Instructions, 02/2018, C79000-G8976-C468-02