Siemens TIM 1531 IRC Operating Instructions Manual page 84

Telecontrol
Table of Contents

Advertisement

Configuration
4.13 Communication with the CPU
Table 4- 2
Coding for substitute path
● Configured interface
The TIM interfaces "Ethernet 1" (IE1), "Ethernet 2" (IE2), "Ethernet 3" (IE3) and WAN1
are numbered through from 0 . 3 (decimal):
– 0 = Ethernet interface IE1 (X1)
– 1 = Ethernet interface IE2 (X2)
– 2 = Ethernet interface IE3 (X3)
– 3 = Serial interface WAN1 (X4)
● Path status
– Main path = 1. Path (bits 0 + 1)
– Substitute path = 2nd path (bits 2 + 3)
Coding options of byte 1
Same coding of the configured interface for the main and the substitute path means that
there is no path redundancy (only one interface configured). The path status is output via the
bits of the main path (1st path).
84
Assignment of byte 1:
Bits 6 + 7
Configured interface
Status of bit 5
Status of bit 4
(7)
(6)
0
0
0
1
1
0
1
1
Status of bit
Status of bit
1 (3)
0 (2)
0
0
0
1
1
0
1
1
Bits 4 + 5
Coding for main path
Meaning
Coding for Ethernet interface X1 (decimal: No. 0)
Coding for Ethernet interface X2 (decimal: no. 1)
Coding for Ethernet interface X3 (decimal: no. 2)
Coding for serial interface X4 (decimal: no. 3)
Meaning bit 1
Bit 1: Path not current
Bit 1: Path not current
Bit 1: Path current
Bit 1: Path current
Operating Instructions, 02/2018, C79000-G8976-C468-02
Bits 2 + 3
Path status
Substitute path (2nd
Main path (1st path)
path)
Meaning bit 0
Bit 0: Subscriber not reachable
Bit 0: Subscriber reachable
Bit 0: Subscriber not reachable
Bit 0: Subscriber reachable
Bits 0 + 1
TIM 1531 IRC