Configuration
4.9 Ethernet interface
If the router can be reached via a dynamic IP address, there must be at least one available
DNS server in the network.
● MSC port of the router
The port number is preset. If necessary, you can change the port number. Note that the
port number of both partners must be identical. The port number canot be configured for
the station.
Default setting: 26382. Permitted range: 1024...65535
● Host name
If the router should be available using a host name enter it here.
● IP address DNS server
Here, enter the addresses of the DNS servers in the subnet.
MSC monitoring settings
● MSC monitoring time
Monitoring time (minutes) for the MSC connection
– Behavior of the master station:
– Behavior of the station:
Default setting: 10. Permitted range: 0...65535
If you enter 0 (zero), the function is disabled.
● Collect data volume
If the option is enabled, the MSC master passes the monthly transferred data volume of
the stations to online diagnostics.
MSC protocol settings - Ethernet: MSC station/node station
The description applies to the parameter group of the Ethernet interface with the Network
node type "Station" / "Node station".
68
If there is no data traffic between the MSC master and station within the monitoring
time, the MSC master sends a sign-of-life frame to the station.
If the station does not acknowledge the sign-of-life frame, the master station sets the
station to 'Faulty'.
If there is no data traffic with the MSC master station within the monitoring time, the
station sets the center to 'Faulty'.