3

Installation

3.1

Recommendations for the set-up location / operation

– clean, horizontal set-up area
– well vented or ventilated room and one with level set-up area capable of bearing an appropriate load.
– room temperature at least 15°C.
– Sealed floor covering with integrated drain.
– hot and cold water connections
– room height at least 60 cm higher than the grease separator system so that the inspection covers can be
opened during cleaning work.
– free working space of at least 1 m in front of the grease separator system.
– inlet with stilling section of min. 1 m (gradient 1:50). transition from on-site drainpipe to stilling section
equipped with 2x45° bends
– If the inlet pipe is longer than 10 m it must be bled separately.
– Foreign bodies (cutlery, crown corks, mustard sachets, bones, etc.) disrupt or damage separating operation
We recommend fitting a coarse particle strainer.
– If the grease separator system is installed below the locally specified backwater level, a lifting station must be
installed downstream in accordance with DIN EN 1825, unless local regulations specify otherwise.
3.2

Setting up / installing the grease separator system

During installation, the pertinent regulations in EN 1825 and DIN 1986 must be heeded.
When full, the grease separator system is heavy. Ensure that the surface has sufficient load-bearing capacity
(for volume"Technical data", page 15).
Inlet and outlet pipes must be connected on site. After putting into operation, check the connection pipes for
leaks. If water leaks, check the fit of the connections.
The following note applies to system type B only (Variant D)
- The direct disposal pipe must be connected on site.
We recommend use of a fabric hose and 2 screw hose clamps for the connection and 10 Nm torque on
the PE pipe DN 70 with level bead.
If connected to a steel pipe, ensure a restrained joint.
- The Storz-B coupling (R 2 1/2" internal thread) supplied must be installed at the end of the disposal pipe,
in a place easily reached by the disposal vehicle
.
Torques for the screw connections
accordingly.
1) reduction of the risk of sucking empty siphons and odour traps. Less air input and movement and odour formation and
foaming in the separator.
2018/01
Installation
.
1
are listed in Ch5.2 on page 15. Make sure these are heeded
11 / 18