Standard Object Types Supported
Object-Type
Analog Input
Analog Value
Binary Input
Binary Value
Multi-state Input
Multi-state Value
Device
Data Link Layer Options
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
MS/TP master (Clause 9), baud rate(s):
9600, 19200, 38400 & 76800
MS/TP slave (Clause 9), baud rate(s):
9600, 19200, 38400 & 76800
Segmentation Capability
Segmented requests
supported
Segmented responses
supported
www.DaikinApplied.com
a
ppendIx
Creatable
Deleteable
Active_Text, Description, Inactive_Text
Active_Text, Description, Inactive_Text
State_Text
State_Text
Description
Location
Max_Master
Window Size: 4 for IP and 1 for
MS/TP
Window Size: 4 for IP and 1 for
MS/TP
a: p
I
roToCol
mplemenTaTIon
Optional
Device Address Binding
Yes
Static Device Binding
No
Character Sets Supported
ANSI X3.4
IBM
/Microsoft
®
ISO 8859-1
ISO 10646 (UCS-2)
ISO 10646 (UCS-4)
JIS C 6226
NOTE: Support for multiple character sets does not imply
they can be supported simultaneously.
63
ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER
C
s
onformanCe
TaTemenTs
Writeable
COV_Increment, Out_of_Service,
Present_Value, Units
COV_Increment, Present_Value, Priority_Array,
Relinquish_Default, Units
Present_Value
Present_Value, Priority_Array,
Relinquish_Default,
MSV15 = Device Units (English – Metric)
Description
Location (Limit 32 Chars)
Max_Master
DBCS
®
(pICs)