Figure 2: Space Temperature Setpoint Operation
nciStg2SptDiff
nciStg2SptDiff
nciOccDiff
nciOccDiff
nciStg2SptDiff
nciStg3SptDiff
nciStg4SptDiff
ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER
79 Effective Cool Stage 3 ON SP
78 Effective Cool Stage 3 OFF SP
77 Effective Cool Stage 2 ON SP
76 Effective Cool Stage 2 OFF SP
75 Effective Cool Stage 1 ON SP
74 Effective Cool Stage 1 OFF SP
73
Reference Setpoint
72
71 Effective Heat Stage 1 OFF SP
70 Effective Heat Stage 1 ON SP
69 Effective Heat Stage 2 OFF SP
68 Effective Heat Stage 2 ON SP
63 Effective Heat Stage 3 OFF SP
62 Effective Heat Stage 3 ON SP
57 Effective Heat Stage 4 OFF SP
56 Effective Heat Stage 4 ON SP
s
paCe
0.5 (Effective Deadband)
0.5 (Effective Deadband)
60
T
s
m
emperaTure
eTpoInT
Effective Deadband
www.DaikinApplied.com
eThods
Need help?
Do you have a question about the MicroTech III and is the answer not in the manual?
Questions and answers