Bacnet Data Points - Smartsource Single And Two - Daikin MicroTech III Sales And Engineering Data Sheet

Water source heat pump unit controller protocol information
Hide thumbs Also See for MicroTech III:
Table of Contents

Advertisement

BACnet Data Points - SmartSource Single and Two Stage Compressor, Enfinity
Large Two Compressor
SmartSource (Series2) Models: GSH/GSV, GTH/GTV and GCV
Enfinity Models: (SS2C) CCH/CCW, and LVC/LVW
Table 8: Analog Inputs - SmartSource Single and Two Stage, Enfinity Large Two Compressor
Object
Point Name
Type/
Instance
Local Space
AI:1
Temperature Output
Leaving Water
AI:2
Temperature
Entering Water
AI:3
Temperature
Discharge Air
AI:4
Temperature
Local Setpoint Adjust
AI:5
Output
Compressor #1
AI:6
Suction Temperature
Compressor #2
AI:7
Suction Temperature
Brownout Voltage
AI:8
Reading
ED 15103-6 • MICROTECH III WSHP UNIT CONTROLLER
Read/
BACnet Object
Write
Name
Access
2
ANALOG INPUTS
R
LocalSpaceTemp
R
LWT
R
EWT
R
DischAirTemp
R
LocalSetpt
CompSuctionTemp
(SmartSource)
R
Comp1
SuctionTemp
(SS2C)
CompDischTemp
(SmartSource)
R
Comp2
SuctionTemp
(SS2C)
R
Brownout
Non-
Range/Default
volatile
(in Units)
Memory
1
0 to 158ºF
The value of the hardwired space temperature sensor
-17.77 to 70ºC
installed either in the return air or the space. Writing to
N
Space Temp Input (AV18) does not affect Local Space
Default:
Temp (AI1) but does affect Effective Space Temp (AV22).
68ºF / 20ºC
0 to 158°F
-17.77 to 70°C
N
Indicates the Leaving Water Temperature sensor value.
Default:
32ºF / 0ºC
0 to 158°F
-17.77 to 70°C
N
Indicates the Entering Water Temperature sensor value.
Default:
32ºF / 0ºC
0 to 158°F
-17.77 to 70°C
N
Indicates the discharge air temperature sensor value.
Default:
32ºF / 0ºC
The reference setpoint used to determine the Effective
55 to 95ºF
Heating/Cooling setpoints. It is the value of the local,
12.78 to 35ºC
hardwired space temperature setpoint. It is only valid if the
N
unit controller JP5 configuration jumper is configured for
Default:
Long Range Setpoint Adjust and is enabled by MSV14.
32ºF / 0ºC
See
0 to 158°F
-17.77 to 70°C
Indicates the compressor #1 suction line temperature
N
sensor value.
Default:
32ºF / 0ºC
Indicates the compressor #2 suction line temperature
0 to 158°F
sensor value for Enfinity Large Two Compressor (SSC2)
-17.77 to 70°C
units.
N
Default:
This variable is not supported by SmartSource unit
32ºF / 0ºC
controllers.
The Brownout Voltage Reading is compared to the
0 to 1023 counts
N
reference setpoint to determine if the brownout condition
Default: 0
exists.
14
C
omprehensIve
Description
Effective Occupancy
Modes.
6
6
www.DaikinApplied.com
d
T
aTa
ables
6
6
6
6
6